Cable Fault Locating System
COMPAC 12 is a compact, rugged system designed for quick and accurate cable fault detection in power cables, ideal for utilities, industrial plants, and service providers. It integrates advanced diagnostic tools for fault pre-location and stabilization in one unit, offering up to 12kV voltage capability and 750J energy delivery with essential safety features like output cable interlock, emergency OFF, and automatic discharge.
Pre-location modes include TDR, ICM, and ARM. Additional functions include DC Hi-Pot testing for insulation integrity (up to 12kV, 20mA with overcurrent trip), sheath fault location and burn/proof testing (12kV DC, up to 50mA) to stabilize faults for faster pre-location.
Rated energy output of 750 Joules at each selectable range
Pre-location of cable faults distance with TDR, ICM
& ARM Methods
DC Hi-pot, Burn test & SFL up to 12 kV
Maximum measuring range of 100 km
Battery/Power Backup
GPS based Cable Route Mapping
Technical Specifications
| Impulse Mode | |
| Voltage range | 0 – 6 kV / 0 – 12 kV selectable & continuously variable |
| Energy | 750 J (full energy at each range) |
| Single Impulse | Yes |
| Selectable auto frequency per minute | Programmable |
| ARC module | Yes |
| ARC Stabilization Time | 20ms approx |
| Indication | ON/OFF lamp indication, Overheat indication |
| DC Test Mode | |
| Voltage Range | 0 – 12 kV continuously variable (two stage) |
| Current | 5 / 10 / 20 mA |
| Burn Current | 50mA at 12kV |
| Sheath Test | |
| Voltage | 0 – 12kV continuously variable |
| Current | 50mA |
| Pre-locator | |
| Maximum measuring range | 100km |
| Pre-location modes | TDR, ICM, ARM(MIM) |
| Resolution | 0.1m |
| Sampling Rate | 200MHz |
| Pulse Width | 40ns – 7µs |
| Pulse Amplitude | 65V |
| VOP (V) m / µs | 90 – 300m/ µs |
| Display | 1200 x 800 px – 10 inch, color touchscreen LCD |
| No of records storage memory | > 100 |
| Communication interface | USB |
| Control | Touchscreen and mousepad |
| General Parameters | |
| Input Power Supply | 230V AC ± 10% |
| Power Frequency | 50Hz or 60Hz ± 5% Single Phase |
| Battery (Auxiliary Source) | Li-ion 25.2V, 8400mH |
| Battery backup – approx. | 30 min |
| Battery charger | 110 – 220V AC – 50Hz , 8.4V/3A DC |
| Earth Discharge | Soft automatic discharge through in-built solenoid |
| Dimensions (H X W X L) approx. | 700mm x 425mm x 620mm |
| Weight | 80kg |
| Safety | |
| Safety Protection | Output HV cable interlock, Over Heat protection, Emergency OFF and Keylock |
| Overload Protection | Input Current Limiter switch, fast blow fuse in mains and controlled supply |